1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
Inspection Information
Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
May 2, 2024
Number of critical violations
1
Number of non-critical violations
3
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
313
Critical Operations and Maintenance /Other (specify below)
Water System placed on a Boil Water Notice due to Treatment System Disconnected and not maintained - UV Sensor disconnected and bacteriological sampling not maintained. (Last sample received September 2020). ENSURE ALL WATER USERS NOTIFIED.
Corrective Actions: -As discussed submit bacteriological samples this coming Monday. -Have Technician repair and maintain Treatment System as soon as possible, once operating flush Distribution System and then re-submit bacteriological as soon as reasonably possible. -Boil Water Notice remains in place until rescinded in co-ordination with Drinking Water Officer.
318
Non-Critical Inadequate Microbiological Analysis data
-Immediately start maintaining semi-monthly sampling. (RAW Source and General Store).
319
Non-Critical Inadequate Chemical Analysis Data
Last Well chemistry from 2014 on file, required to be maintained every five years.
Corrective Actions: Provide updated test with in six months (copy of parameters provided).
322
Non-Critical Emergency Response Plan
Primary Emergency Response Plan on file from 2013 (Previous Owner).
Corrective Actions: Update in one month.