Inspection Information
Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
January 23, 2019
Number of critical violations
1
Number of non-critical violations
2
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
311
Critical Interruption of Treatment
Corrective Actions: The alarm for the UV was activated (beeping) at time of inspection and a valve on a line that bypasses the solenoid valve was open. The bypass line must removed to prevent untreated water from entering the system when the solenoid valve closes; until the cause of the alarm is identified and repaired all users must be advised to boil their water prior to use.
318
Non-Critical Inadequate Microbiological Analysis data
Corrective Actions: Records indicated that only two samples were submitted for bacteriological testing in 2018. Water samples must be submitted weekly to ensure compliance with the Drinking Water Protection Regulation (A minimum of four samples per month are required)
319
Non-Critical Inadequate Chemical Analysis Data
Corrective Actions: As a requirement of the Operating Permit terms and conditions, a chemical analysis of the source water is required once every 5 years. This was last done in 2011, ensure this is completed in 2019.