1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
Inspection Information
Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
September 1, 2021
Number of critical violations
0
Number of non-critical violations
3
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
317
Non-Critical Inadequate or improper construction of water works
Changes to system (sand filters and UV). Previous site map/treatment system schematic insufficient. Provide a: - Detailed, labelled site map of the property. Show source, septic, distances, water lines, connections, structures, etc. - Detailed treatment schematic of the current system, going from source to the end. Include all specifications and specifics on the makes/models. Provide clear photos to support.
Corrective Actions:
319
Non-Critical Inadequate Chemical Analysis Data
Last chemical/physical analysis on file from 2014. These need to be done every 5 years. Operator stated that a recent full analysis was done for another program (GAP?). Submit a copy to this office to review. If insufficient, then a full chemical/physical analysis of the raw, untreated water needs to be completed.
Corrective Actions:
321
Non-Critical Inadequate Treatment
Facility on a Boil Water Notification (2017). Current system design does not meet Surface Water Treatment objectives. Upgrades will be required. Baseline information needs to be updated.