1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
Inspection Information
Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
August 1, 2024
Number of critical violations
1
Number of non-critical violations
3
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
312
Critical Inadequate Treatment
The water system is served by a surface water source, Haggard's Lake. There is no treatment on this water system. There is no electrical power available onsite. Some of the dwellings do have solar; however, during the winter month's this is not reliable.
Corrective Actions: All water systems in BC must meet Drinking Water Treatment Objectives (Microbiological) for Surface Water Supplies in British Columbia Version 1.2 / First Published November 2012. There are currently barriers to meeting these standards. The following is required: 1. Develop a plan to meet these treatment standards.
318
Non-Critical Inadequate Microbiological Analysis data
Currently no bacteriological sampling is occurring. The Drinking Water Protection Regulation requires at least 4 samples/month for a system this size; however, the system is currently on a long term boil water notice and is remote. Considering this, the system will be asked to sample at a reduced frequency.
Corrective Actions: 1. Develop a sampling program that includes a sample submission of once/month at representative locations (close to the pumphouse, and the farthest points on the left and right side of the distribution system). 2. Complete sampling as per the submitted plan.
319
Non-Critical Inadequate Chemical Analysis Data
A chemical analysis has not been completed since 2009.
Corrective Actions: Complete chemical analysis as per the provided parameters, and submit the results to our office. Ensure this testing is done at least every 5 years.
322
Non-Critical Emergency Response Plan
An emergency response plan has not yet been completed. The drought component has been submitted.
Corrective Actions: Complete the emergency response plan and submit it to our office. Ensure to review this plan annually and submit any changes to our office.