1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
Inspection Information
Facility Type
15 - 300 Connections
Inspection Type
Routine
Inspection Date
December 12, 2023
Number of critical violations
2
Number of non-critical violations
4
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
311
Critical Interruption of Treatment
Disinfection treatment (chlorine injector and UV unit) are malfunctioning and/or unplugged.
Corrective Actions: Equipment must be repaired and functioning as designed as soon as possible.
312
Critical Inadequate Treatment
No disinfection equipment was functioning during inspection. Surface water sources must be adequately disinfected to meet water quality standards per Ministry of Health's "Drinking Water Treatment Objectives (Microbiological) for Surface Water Supplies in British Columbia".
318
Non-Critical Inadequate Microbiological Analysis data
Bacteriological sampling not completed at required frequency. No bacteriological results available for 2022/2023. Reviewed sampling procedure during inspection.
Corrective Actions: Sample must be collected and submitted at least once per month for bacteriological analysis.
319
Non-Critical Inadequate Chemical Analysis Data
Most recent chemical/physical analysis of raw source water completed in 2016. Chemical analysis must be completed every 3-5 years and results shared with the Drinking Water Officer (DWO). Page
320
Non-Critical Interruption of Treatment
Filter containing "Ecomix" media showing error message.
Corrective Actions: Ensure filter is repaired and functioning properly.
323
Non-Critical Other
Chlorine test kit is outdated and missing instructions/components.
Corrective Actions: Ensure an up-to-date method of monitoring chlorine residual is in use when chlorine injector is repaired and functioning. Maintain records of chlorine residual and maintenance works on the system.