1952 Bay Street Victoria, B.C. V8R 1J8 | Visit Official Website (opens in a new tab)
Inspection Information
Facility Type
2-14 Connections
Inspection Type
Routine
Inspection Date
March 27, 2019
Number of critical violations
2
Number of non-critical violations
2
Violations:
A summary of the violations found during the inspection are listed below.Code
Description
311
Critical Interruption of Treatment
UV system in alarm. Operator ordering new bulbs. All facilities (except store) closed until summer season. Replace bulb. Flush all lines. Ensure equipment is functional and is providing adequate treatment. Do not reuse filters.
Corrective Actions:
313
Critical Operations and Maintenance /Other (specify below)
Submit a detailed, accurate, labelled site map showing water system, system lines, treatment train, source, septic system. etc.
Corrective Actions:
318
Non-Critical Inadequate Microbiological Analysis data
Full chemical analysis of well raw water quality needed. EHO to follow up.
Corrective Actions:
319
Non-Critical Inadequate Chemical Analysis Data
No bacteriological water samples submitted since August 2017. EHO to send requisitions. Begin sampling on bimonthly basis.
Corrective Actions: